FM9 Condenser Fan Speed Contol

Product Details

share product

The FM series monophase fan speed control units keep the condenser gas pressure constant by adjusting the fan speed according to the condenser pressure or temperature. In addition to the pressure and temperature sensors, 0-5V, 0-10V or potentiometer can also be connected to provide external control. The soft-start feature softens the fan’s first attempt. In cold weather, the fan applies full power for a short period of time at the start of the fan, thus resolving problems such as fan congestion, snow accumulation, etc. The user-friendly menu allows easy operation without confusion. The desired fan speed can be adjusted in the band frame that the user can adjust.

The FM control units also offer solutions to the needs of monophase motors (suitable for control with phase angle control), heating and dimmers. In addition to temperature, pressure and analogue inputs, other control requirements also provide a complete solution thanks to the increasing or decreasing sloping output function in the band frame that the user can adjust.

FEATURES

  • Hardware that adjusts the fan speed according to the condenser pressure or temperature and keeps the condenser gas pressure constant
  • Possibility to control from outside by connecting 0-5V, 0-10V potentiometer as well as pressure and temperature sensors
  • Soft start-up with soft-start (fan)
  • User-friendly menu for easy operation
  • User can adjust the desired fan speed in band frame that can be adjusted
  • Adjusting the speed of monophase motors (suitable for control by phase angle method), solution to needs such as heater and dimmer
  • 6, 9, 12, 16 amp models for different capacities and needs
  • Easy installation, direct mounting
  • Compact and robust design

TECHNICAL INFORMATIONS

  • Programming: 4 digits 7 segment LED display with 3 buttons, Easy Glide technology
  • Speed control: Phase cutoff voltage regulation (SCR)
  • Operating voltage: 230V +/- 10%
  • Max. Fan Amp: 9A
  • Operating frequency: 50Hz / 60Hz, automatic selection
  • Input type: Pressure, temperature, Voltage, RS485 (optional)
  • Pressure transmitters: Ratiometric 5V supply, 0.5-4.5V full scale
  • Pressure range: Any pressure range ratiometric sensor can be used
  • Temperature sensor: 10K NTC Thermoplastic
  • Operating range: -40 .. + 120oC
  • Voltage control: 0-5V / 0-10V
  • Measurement accuracy: +/- 0.1% 12bit ADC interpolation
  • Dimensions: 134x134x84mm
  • Box size: 143x143x80mm
  • Weight: 690gr

USAGE ARES

  • Condenser fan speed control
  • Air conditioning